Underground Burial Cover-Depth Lookup (NEC Table 300.5)

Returns the minimum cover for underground wiring by method and location from NEC Table 300.5 (<= 1000 V): direct-burial cable 24 in, PVC 18 in, RMC/IMC 6 in in general earth, all methods 24 in under public streets/driveways, and 0 in (in raceway) under a building. Cover is measured to the top of the raceway/cable; the table footnotes modify specific cells and the AHJ governs.

Run the calculator

Formula and source

min_cover (in) = Table 300.5 cell for (wiring method, location); cover is measured to the top of the raceway/cable. General earth: direct burial 24, RMC/IMC 6, PVC 18, residential GFCI branch 12, low-voltage 6.

Minimum cover requirements, 0 to 1000 volts, NEC 2023 Table 300.5, by name.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.