COP Implied by the Heat of Rejection

The COP implied by a measured or rated heat of rejection and the evaporator capacity.

Run the calculator

Example

You enter

You get

Details, formula, and sources

COP = Q_evap / (THR - Q_evap), with the compressor work THR - Q_evap. A system absorbing 60,000 Btu/h and rejecting 100,000 runs a COP of 1.5. Reads the operating efficiency off the condenser duty. Hermetic motor heat inflates the measured THR and lowers the apparent COP. An engineering aid; the rated data govern.

COP = Q_evap / (THR - Q_evap), the inverse of THR = Q_evap (1 + 1/COP); W_comp = THR - Q_evap; factor = THR / Q_evap. Requires THR > Q_evap.

The condenser total heat of rejection THR = Q_evap (1 + 1/COP), a standard refrigeration-cycle result, solved for the COP, by name.

The total-heat-of-rejection relation is a public refrigeration-cycle result; the ASHRAE Handbook covers condenser sizing.

Estimate. AHJ and licensed professional govern.

Field names used by the API: q_evap, target_thr, cop, w_comp_btuh