Cooling Tower Approach and Range

Range, approach, heat rejection (gpm × 500 × range BTU/hr).

Run the calculator

Example

You enter

You get

Details, formula, and sources

Range, approach, heat rejection (gpm × 500 × range BTU/hr), and fan kW per ton against typical 5-10 °F approach / 8-12 °F range targets.

Range = T_in − T_out. Approach = T_out − T_wb. Efficiency = range / (range + approach) = range / (T_in − T_wb). Heat rejection (BTU/hr) = gpm × 500 × range. Fan kW per ton = fan_kW × 12000 / heat_rejection.

Cooling Technology Institute (CTI) ATC-105 standard practice by name; ASHRAE Handbook (HVAC Systems and Equipment) cooling-tower chapter by name.

CTI guides free at cti.org outreach; ASHRAE Handbook licensed.

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: T_in_F, T_out_F, T_wb_F, gpm, fan_kW, range_F, approach_F, efficiency, heat_rejection_BTU_hr, approach_flag, range_flag, fan_kW_per_ton