Duct Leakage Test-and-Balance
SMACNA leakage class from measured-vs-design CFM at test pressure; pass/fail against the design class.
Formula and source
leakage_cfm = design_cfm - measured_cfm. leak_at_1inwc = leakage_cfm / sqrt(test_pressure_inwc) (orifice-flow scaling). leak_per_100ft2 = leak_at_1inwc / duct_surface_ft2 × 100. Effective class = smallest SMACNA class (3, 6, 12, 24, 48) whose limit ≥ leak_per_100ft2.
SMACNA Duct Leakage Test Manual (3rd ed.) by name. ASHRAE 90.1-2022 §6.4.4.2-2022 (Ventilation for Acceptable Indoor Air Quality). (referenced for the leakage-class system).
Audience
This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.
Related tools
Posture
Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.