Air-Side Economizer Free-Cooling Hours

Free-cooling capacity and the annual ton-hours an air-side economizer offsets.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Sensible free-cooling capacity (BTU/hr) and annual ton-hours of mechanical cooling offset from supply airflow and the mix-to-supply delta-T over the economizer-eligible hours.

Q_sens = 1.08 * CFM * dT (sensible heat, standard air); ton-hours = Q_sens * hours / 12,000. dT is the mix-to-supply delta-T.

ASHRAE sensible-heat relation Q = 1.08 * CFM * dT (public); air-side economizer changeover per ASHRAE Standard 90.1, by name.

ASHRAE 90.1 free read-only at ashrae.org; the 1.08 sensible factor is public.

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: cfm, delta_t_f, hours, q_sens_btuh, ton_hours