Evaporative (Swamp) Cooler Leaving Temperature

The supply-air temperature a direct-evaporative (swamp) cooler delivers.

Run the calculator

Example

You enter

You get

Details, formula, and sources

T_out = T_db - saturation effectiveness x (T_db - T_wb). 95 F dry-bulb, 65 F wet-bulb, and an 85% pad give 69.5 F. The wet-bulb depression is the maximum possible drop, so a dry climate cools far more than a humid one; the process adds moisture (high leaving RH). Pad effectiveness ~0.80-0.90 rigid media, less for aspen. Direct single-stage only; the equipment data govern.

T_out = T_db - saturation_effectiveness x (T_db - T_wb); temp_drop = effectiveness x (T_db - T_wb); wet_bulb_depression = T_db - T_wb.

ASHRAE Fundamentals direct-evaporative (saturation) effectiveness relation, by name; classical psychrometrics.

The saturation-effectiveness relation is free in published engineering texts.

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: dry_bulb_F, wet_bulb_F, effectiveness, leaving_db_F, temp_drop_F