Filter Area for a Target Loading Rate

The filter area needed for a target loading rate at the design flow.

Run the calculator

Example

You enter

You get

Details, formula, and sources

area = flow / target loading. 800 GPM at 4 gpm/ft^2 needs 200 ft^2 of media; the backwash flow that area draws (15 gpm/ft^2 default) is reported and the loading band named. Answers 'how big a filter' instead of the rate from one area. AWWA general practice; the operator of record and the state primacy agency govern.

Required filter area (ft²) = design_flow / target_loading. Backwash flow = backwash_rate × area. Bands: rapid sand 2-5 gpm/ft², high-rate 5-8 gpm/ft².

Ten States Standards (Recommended Standards for Water Works), Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, current edition by name. AWWA B100 / B130 (filter media) by name.

Ten States Standards licensed; principles free in published water-treatment texts.

Estimate. Operator of record and primacy agency govern.

Field names used by the API: flow_gpm, target_loading_gpm_ft2, backwash_rate_gpm_ft2, required_area_ft2, backwash_gpm