Generator Output Conductor at 115% (NEC 445.13)
The conductor rule from a generator to its first overcurrent device, which estimators routinely get wrong.
Example
You enter
- Generator real power (kW, used if nameplate is 0) 150
- Voltage (V, line-to-line 3ph or line-to-neutral 1ph) 480
- Phase 3
- Power factor 0.8
- Generator design false
You get
- Nameplate current 225.6 A
- Applied basis 115% of nameplate
- Required conductor ampacity 259.4 A
Details, formula, and sources
NEC 445.13(A) sets the ampacity at not less than 115% of the generator NAMEPLATE current -- not 125% of a computed load, not the connected running load. A 150 kW, 480 V three-phase generator at 0.8 pf draws 225.6 A nameplate, so the conductor must carry 1.15 x 225.6 = 259.4 A. Where the design prevents output above nameplate (overload-limited), the basis drops to 100% and it is just 225.6 A. Enter the nameplate current directly or derive it from kW, voltage, phase, and pf. The 110.14(C) termination limit and 310.15 adjustments still apply. A design aid; the AHJ governs.
nameplate = given, or kW x 1000 / (sqrt(3) x V x pf) three-phase, or kW x 1000 / (V x pf) single-phase; basis = overload_limited ? 1.00 : 1.15; required_ampacity = basis x nameplate.
The generator output-conductor ampacity rule of NEC 2023 445.13(A) -- not less than 115% of the generator nameplate current, or 100% where the design prevents output above the nameplate -- by name. A computational aid; the AHJ-adopted NEC edition governs.
NEC is free to read at nfpa.org/freeaccess. The 115% basis is on the nameplate current, not 125% of a computed load; the 110.14(C) termination limit and 310.15 ambient/fill adjustment are stated as out of scope, not modeled.
Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.
Field names used by the API: gen_kw, voltage_v, phase, power_factor, overload_limited, nameplate_a, basis, required_ampacity_a
- Basis 115% of the generator nameplate current for output conductors; 100% where the design prevents output above nameplateNEC 445.13(A)
- Nameplate supplied directly, or derived from kW, voltage, phase, and power factorgenerator nameplate
- Downstream the conductor still must satisfy the 110.14(C) termination limit and any 310.15 adjustmentNEC 110.14(C) / 310.15