Generator Sizing for Motor Starting

Required generator kW / kVA from running load and motor-starting kVA at the 30% voltage-dip criterion.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Steady kW = Σ running_kW + non_motor_kW. Worst starting kVA = max over motors of starting_kVA(motor); starting_kVA = HP × code_kVA_per_HP from the NEMA MG-1 code letter, OR LRA × V × √phases / 1000 if the user supplies LRA. Required gen kVA = worst_starting_kVA / dip_factor (0.30 default per the 30% voltage-dip criterion). Required kW = max(steady, required_starting_kVA × 0.8).

NEMA MG-1 (Motors and Generators) by name; engineering-practice 30% voltage-dip criterion for transient motor starts.

NEMA MG-1 licensed; code-letter principles free in published power-engineering texts.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: motors, non_motor_kW, dip_factor, starts_per_hour, running_kW, worst_starting_kVA, required_starting_kVA, required_kW, recommended_kW