Low-Ambient Head Pressure Control and Winter Charge

The lowest head pressure a system can be allowed to run at in cold weather.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The lowest head pressure a system can be allowed to run at in cold weather, and the extra refrigerant that holding it takes. The expansion valve does not care about head pressure as such -- it cares about the pressure DIFFERENCE across itself, because that is what drives flow through the orifice. As ambient falls, condensing pressure falls with it, the difference across the valve shrinks, and at some point the valve can no longer feed the coil. The minimum head pressure is therefore built up from the bottom: whatever the evaporator is at, plus the drop the valve needs at full load, plus everything lost in the distributor and the liquid line. Fan cycling is the cheap fix and it is coarse, because head pressure swings between fan stages and on a multi-fan condenser in a cold, windy location it may not hold at all. Flooding the condenser is the fix that works: a head-pressure-control valve backs liquid up into the condenser, reducing its effective surface until it can only reject heat at an acceptable pressure. That backed-up liquid is real refrigerant and it has to be in the system, which means a receiver sized to hold it in summer and a winter charge substantially above the summer one. A system at 20 psig evaporator with a valve needing 100 psi and 15 psi of line losses must hold 135 psig, and a 0.35 cubic ft condenser flooded 80% at 70 lb per cubic foot backs up 19.6 lb -- which in summer, when the condenser drains, all has to live in the receiver. Systems converted to flooded-condenser control without adding charge starve in exactly the weather they were supposed to fix. A design screen; the equipment manufacturer's data, the control valve's setting, and a qualified refrigeration engineer govern.

min_head_psig = evaporator_psig + valve_dp_psi + line_losses_psi; the saturated condensing temperature is read from the P-T table at that pressure; flooding_charge_lb = condenser_volume_cf x flooded_fraction x liquid_density_pcf; winter_charge = summer_charge + flooding_charge.

Minimum head pressure built up from the evaporator pressure plus the expansion valve's required pressure drop plus distributor and liquid-line losses, by name, with the flooding charge from the condenser's internal volume at the design flooded fraction. The saturated condensing temperature is read from the same bundled P-T tables this module already carries for its P-T tile. The equipment manufacturer's data, the control valve's setting, and a qualified refrigeration engineer govern.

The pressure build-up and the flooding volume are arithmetic on the system's own values; the P-T data is the module's existing bundled table, already cited by its own tile.

Estimate. AHJ and licensed professional govern.

Field names used by the API: refrigerant, evaporator_psig, valve_dp_psi, line_losses_psi, condenser_volume_cf, flooded_fraction, liquid_density_pcf, receiver_capacity_lb, summer_charge_lb, min_head_psig, min_condensing_f, flooding_charge_lb, winter_charge_lb

Related tools