Landfill Gas Flare Capacity and Destruction

Sizes an enclosed flare from the peak gas flow and a design margin.

Run the calculator

Example

You enter

You get

No published worked example is on file for this calculation. It is checked against a hand-worked derivation of its method and an independent reference test.

Details, formula, and sources

ScopeWith the minimum stable flow from its turndown and the methane destruction credit. The worked flare reaches its turndown only after decades, but a well field pulled too hard takes the gas to 182 Btu/cu ft and trips it in a week.

Formula or tablerated capacity = peak flow x (1 + design margin); minimum stable flow = rated / turndown ratio; heat release = methane flow x heating value; credit = methane mass destroyed x its global warming potential.

Source and editionFlare sizing against the manufacturer's rated capacity and turndown. A flare needs roughly 20% methane to hold a flame. The site's gas analysis and the applicable air permit govern.

Free accessPublic arithmetic; the turndown and rated capacity come from the flare manufacturer.

What governsEstimate. AHJ and licensed professional govern.

API field namespeak_lfg_cfm, methane_fraction_pct, design_margin_pct, turndown_ratio, methane_heating_value_btu_per_cf, destruction_efficiency_pct, global_warming_potential, reduced_methane_fraction_pct, methane_density_lb_per_cf, methane_cfm, rated_capacity_scfm, heat_release_mmbtu_per_hr, minimum_stable_scfm, design_btu_per_cf, reduced_btu_per_cf, methane_lb_per_year, methane_destroyed_tons, co2e_tons