LED Lighting Retrofit Savings and Payback

The four numbers on every lighting proposal.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The energy saved from the wattage reduction (fixtures x (W_old - W_new) x hours x rate), the demand-charge reduction if the load runs at the utility peak, the total annual saving, and the simple payback against install cost. The demand term, which a lighting proposal that ignores the demand side omits, often shortens the payback by a third. The burn hours are the actual operating hours; a controls retrofit is a separate credit and an air-conditioned space gains a cooling credit not included here. A simple payback, not a life-cycle analysis.

kw_saved = fixtures x (watts_existing - watts_new) / 1000; kwh_saved = kw_saved x annual_hours; energy_usd = kwh_saved x rate_kwh; demand_usd = kw_saved x demand_per_kw_mo x 12; annual_usd = energy_usd + demand_usd; payback_years = install_cost > 0 ? install_cost / annual_usd : null.

The standard energy-and-demand lighting-retrofit savings method (kWh_saved = fixtures x (W_old - W_new) / 1000 x hours, demand savings at the utility's $/kW-month, simple payback = cost / annual savings), by name; the relations are public.

The energy-and-demand savings relations and simple payback are public arithmetic; DOE and utility retrofit worksheets are free.

Estimate. AHJ and licensed professional govern.

Field names used by the API: fixtures, watts_existing, watts_new, annual_hours, rate_kwh, demand_per_kw_mo, install_cost, kw_saved, kwh_saved, energy_usd, demand_usd, annual_usd, payback_years