Motor Branch-Circuit Protection and Disconnect (NEC 430.52 / 430.110)

Sizes the maximum motor branch-circuit short-circuit and ground-fault protective device from the table FLC and device type per NEC Table 430.52 (250% inverse-time breaker, 175% dual-element fuse, 300% nontime-delay fuse, 800% instantaneous-trip), with the 430.52(C)(1) Exception 1 round-up to the next standard size (240.6), plus the 430.110 disconnect at 115% of FLC. Overload is sized separately (430.32); the AHJ governs.

Run the calculator

Formula and source

max_ocpd = FLC x Table 430.52 multiplier (inverse-time breaker 250%, dual-element fuse 175%, nontime-delay fuse 300%, instantaneous-trip breaker 800%); round up to the next standard size (240.6) per 430.52(C)(1) Exception 1; min disconnect = 1.15 x FLC (430.110).

Motor branch-circuit short-circuit and ground-fault protection, NEC 2023 430.52 and Table 430.52, with the disconnect ampere rating 430.110, by name.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.