Parallel Conductor Ampacity

Total ampacity of N paralleled conductor sets with the NEC more-than-three current-carrying-conductor and ambient adjustments, plus per-set load adequacy (1/0 AWG and larger only).

Run the calculator

Formula and source

I_total = I_single x N x F_ccc x F_ambient, where N is the number of identical parallel sets, F_ccc is the more-than-three current-carrying-conductor adjustment (1.0 for <=3, 0.8 for 4-6, 0.7 for 7-9, 0.5 for 10-20, ...), and F_ambient the temperature correction. Per-set current I_set = I_load / N. Paralleling is permitted only at 1/0 AWG and larger.

NEC (NFPA 70) Article 310 paralleled-conductor provisions and the 310.15(C)(1) adjustment factors, by name.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.