Pitot Traverse Airflow (Velocity Pressure to CFM)

Duct airflow from a Pitot traverse reading.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Field airflow from a Pitot traverse: V = 4005 x sqrt(VP_avg) for standard air, then CFM = V x duct area. 0.15 in wc in a 24x12 duct -> 1551 fpm, 2.0 ft^2, 3102 CFM; a lighter 0.05 in wc reads 896 fpm (the square-root relation). This takes one pre-averaged VP; to average raw point readings the right way, use the velocity-averaged traverse. A field measurement, not a substitute for a calibrated flow station.

V = 4005 sqrt(VP_avg); A = (w x h)/144; CFM = V x A.

The Pitot-traverse airflow measurement (velocity-pressure to velocity, standard air) from ASHRAE Fundamentals / AABC-NEBB field practice, by name.

The V = 4005 sqrt(VP) standard-air relation and the traverse-average method are standard published air-balancing procedures.

Estimate. AHJ and licensed professional govern.

Field names used by the API: vp_avg_inwc, w_in, h_in, v_fpm, area_ft2, cfm