NEC Pull and Junction Box Sizing

The minimum pull or junction box dimension for large raceways under NEC 314.28.

Run the calculator

Example

You enter

You get

Details, formula, and sources

8x the largest raceway for a straight pull, 6x plus the same-row others for an angle or U pull, and the 6x between-entries rule. box-fill is the separate 314.16 conductor-volume fill.

Straight pull: min = 8 x largest raceway. Angle/U pull: min = 6 x largest raceway + sum of same-row others. Between same-conductor entries: >= 6 x larger raceway.

NEC (NFPA 70) 314.28(A)(1) and (A)(2) (by name).

NFPA 70 free read-only at nfpa.org (registration); the multipliers are stated, not reproduced.

Estimate. AHJ and licensed professional govern.

Field names used by the API: pull_type, largest_raceway_in, governing, straight_min, angle_min, between