PV Interconnection 120% Busbar Rule

Load-side PV breaker check against the NEC 705.12 busbar limit (120% opposite-end allowance / 100% otherwise).

Run the calculator

Example

You enter

You get

Details, formula, and sources

With the supply-side 705.11 alternative.

Load-side: sum = main + PV_existing + PV_proposed; limit = 1.20 * busbar (breaker at the opposite end of the busbar from the main, NEC 705.12(B)(3)(2)) or 1.00 * busbar (other load-side position, 705.12(B)(3)(1)); pass when sum <= limit. Supply-side connection (705.11) is ahead of the service disconnect and is not subject to the busbar rule.

NEC 2023 (NFPA 70). Article 705 (705.11 supply-side; 705.12 load-side busbar).

Free read-only access at nfpa.org/freeaccess.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: main_breaker_a, busbar_rating_a, pv_proposed_a, method, sum_of_breakers_a, limit_a, passes