Radiant Floor Heat Output

How much heat a radiant floor puts out per square foot, and whether the surface stays comfortable.

Run the calculator

Example

You enter

You get

Details, formula, and sources

q = 2 x (T_surface - T_room)^1.1 Btu/hr-ft^2, with the ~85 F surface comfort cap (~39 Btu/hr-ft^2 in a 70 F room). An 85 F floor over a 70 F room gives 39.3; solving inverse, a 30 Btu/hr-ft^2 load needs an 81.7 F surface. Solves either direction. The panel manufacturer's ratings and the loop layout govern.

q = 2 x (T_surface - T_room)^1.1 Btu/hr-ft^2; inverse T_surface = T_room + (q/2)^(1/1.1); comfort cap ~85 F surface.

The radiant-floor heat-output relation q = 2 (Tsurface - Troom)^1.1 with the ~85 F surface comfort limit, from ASHRAE / radiant-panel practice, by name.

The floor heat-output correlation and the ~85 F comfort limit are standard published radiant-heating results.

Estimate. AHJ and licensed professional govern.

Field names used by the API: mode, t_surface_f, t_room_f, q_btuh_ft2