Refrigerant Line Velocity and Oil Return

Line velocity from mass flow, inside diameter, and specific volume.

Run the calculator

Example

You enter

You get

Details, formula, and sources

With an oil-return verdict against the riser / horizontal minimum and the ~4000 fpm noise ceiling. Per the ASHRAE Refrigeration Handbook.

V_fpm = (mass_flow_lb_hr * specific_volume_ft3_lb) / area_ft2 / 60, where area = (pi/4)(ID_in/12)^2. Oil return needs a minimum velocity (higher in a suction riser); above ~4000 fpm the line is noisy.

ASHRAE Refrigeration Handbook line-sizing and oil-return guidance, by name.

ASHRAE licensed; refrigerant specific volume is read from the manufacturer's P-T / property data (user-supplied).

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: mass_flow_lb_hr, line_id_in, specific_volume_ft3_lb, orientation, velocity_fpm