Sanitary Drain DFU Sizing

Total drainage fixture units from a fixture list and the minimum pipe size for a horizontal branch, vertical stack.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Total drainage fixture units from a fixture list and the minimum pipe size for a horizontal branch, vertical stack, or building drain. Per IPC 2021 §710 with Table 709.1 DFU values.

total DFU = sum(fixture count × DFU value). Minimum pipe size = smallest size whose table maximum ≥ total DFU: horizontal branch and stack per IPC Table 710.1(2); building drain per IPC Table 710.1(1) (slope-dependent).

IPC 2021 (International Plumbing Code). Section 710; DFU values per IPC Table 709.1; capacities per Tables 710.1(1) and 710.1(2).

Free read-only access at codes.iccsafe.org.

Estimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

Field names used by the API: fixtures, config, slope_in_per_ft, total_dfu, min_size_in