Service Load Calculation (Residential)
Standard demand factors over lighting, appliances, range, dryer, HVAC; output minimum service ampacity.
Example
You enter
- Conditioned area (ft²) 2000
- Small-appliance circuits (min 2) 2
- Laundry circuits 1
- Fixed appliances total (W) 6000
- Range nameplate (W) 12000
- Dryer nameplate (W; 5000 minimum) 5000
- HVAC cooling (W) 5000
- HVAC heating (W) 8000
You get
- Total demand 34225 W
- Required ampacity 142.6 A
- Next standard service 150 A
Details, formula, and sources
Standard method per NEC 220.42 (general lighting demand factors) and 220.82 (optional dwelling-service); appliance loads per NEC 220.53.
NEC 2023 (NFPA 70). Article 220.
Free read-only access at nfpa.org/freeaccess.
Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.
Field names used by the API: area_ft2, small_appliance_circuits, laundry_circuits, fixed_appliances_W, range_W, dryer_W, hvac_cooling_W, hvac_heating_W, total_demand_W, required_A, next_standard_A
- Voltage 240 V single-phase split for dwelling unless user suppliesANSI C84.1 nominal
- Demand factor for first 3 kVA general lighting 100% (per NEC 220.42)NEC 2023