Shock Approach Boundaries (NFPA 70E Table 130.4)

Looks up the NFPA 70E Table 130.4 AC shock approach boundaries by nominal voltage.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The limited approach (separate distances for an exposed movable conductor vs a fixed circuit part) and the restricted approach. Below 50 V no boundary is specified. Shock boundaries only (the arc-flash boundary is separate); the employer's safety program and 70E govern.

lookup by nominal phase-to-phase AC voltage band: limited approach (exposed movable conductor vs exposed fixed circuit part) and restricted approach; below 50 V no boundary is specified.

AC shock approach boundaries, NFPA 70E-2024 Table 130.4, by name.

NFPA 70E is free to read at nfpa.org/freeaccess. These are shock boundaries only; the arc-flash boundary is a separate determination. Crossing the restricted approach requires a qualified person, an energized-work permit, and shock PPE.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: nominal_v_ac, limited_fixed, restricted, no_boundary