Smoke Alarm Count and Placement (IRC R314)
Two halves people confuse. The COUNT is additive and gets undercounted.
Example
You enter
- Sleeping rooms 3
- Separate sleeping areas (one alarm outside each) 1
- Additional stories, incl. basements and habitable attics 1
- Sensing type ionization
- Horizontal distance to the cooking appliance (ft) 8
- Horizontal distance to a tub/shower bathroom door (ft; 0 to skip) 4
You get
- Minimum alarm count 5
- Required cooking (ft) 20
- Cooking deficit (ft) 12
- Bathroom separation 0
Details, formula, and sources
One in each sleeping room, one OUTSIDE each separate sleeping area, and one on each additional story including basements and habitable attics -- three bedrooms, one sleeping area, one extra story is five, minimum. The CLEARANCE depends entirely on the SENSING TYPE, and the spread is better than three to one: 20 ft horizontally from a permanently installed cooking appliance for ionization, 10 ft for ionization with a silencing switch, and 6 ft for photoelectric or an alarm marked to reduce cooking nuisance alarms. So an alarm 8 ft from the range fails as ionization and passes as photoelectric -- in an open plan, changing the type is usually the only way a required location works, and far cheaper than moving it. Also the 3 ft separation from a tub/shower bathroom door.
minimum alarms = sleeping rooms + separate sleeping areas + additional stories; required cooking clearance = 20 ft (ionization), 10 ft (ionization with a silencing switch), or 6 ft (photoelectric, or marked to reduce cooking nuisance alarms); bathroom separation = 3 ft horizontally from the door or opening of a bathroom with a tub or shower.
IRC R314.3 Location and R314.3.1 Installation near cooking appliances.
Both provisions are short prescriptive sentences reproduced in state adoptions and building-department bulletins. No table is reproduced.
Estimate. AHJ and licensed professional govern.
Field names used by the API: sleeping_rooms, sleeping_areas, additional_stories, alarm_type, distance_to_cooking_ft, distance_to_bath_door_ft, required_alarms, required_cooking_ft, cooking_deficit_ft, bath_deficit_ft
- Count each sleeping room + outside each separate sleeping area + each additional storyIRC R314.3
- Story exclusions crawl spaces and uninhabitable attics do not countIRC R314.3
- Cooking clearance 20 ft ionization, 10 ft ionization with silencing, 6 ft photoelectric or nuisance-listedIRC R314.3.1
- Bathroom 3 ft horizontally from the door or opening of a bathroom with a tub or showerIRC R314.3
- Exception separations yield where they would prevent a required location - a documented last resortIRC R314.3 / R314.3.1
- Not checked CO alarms, interconnection, power and battery backup, mounting geometry, existing-dwelling triggersstated scope limit