Smoke Alarm Count and Placement (IRC R314)

Two halves people confuse. The COUNT is additive and gets undercounted.

Run the calculator

Example

You enter

You get

Details, formula, and sources

One in each sleeping room, one OUTSIDE each separate sleeping area, and one on each additional story including basements and habitable attics -- three bedrooms, one sleeping area, one extra story is five, minimum. The CLEARANCE depends entirely on the SENSING TYPE, and the spread is better than three to one: 20 ft horizontally from a permanently installed cooking appliance for ionization, 10 ft for ionization with a silencing switch, and 6 ft for photoelectric or an alarm marked to reduce cooking nuisance alarms. So an alarm 8 ft from the range fails as ionization and passes as photoelectric -- in an open plan, changing the type is usually the only way a required location works, and far cheaper than moving it. Also the 3 ft separation from a tub/shower bathroom door.

minimum alarms = sleeping rooms + separate sleeping areas + additional stories; required cooking clearance = 20 ft (ionization), 10 ft (ionization with a silencing switch), or 6 ft (photoelectric, or marked to reduce cooking nuisance alarms); bathroom separation = 3 ft horizontally from the door or opening of a bathroom with a tub or shower.

IRC R314.3 Location and R314.3.1 Installation near cooking appliances.

Both provisions are short prescriptive sentences reproduced in state adoptions and building-department bulletins. No table is reproduced.

Estimate. AHJ and licensed professional govern.

Field names used by the API: sleeping_rooms, sleeping_areas, additional_stories, alarm_type, distance_to_cooking_ft, distance_to_bath_door_ft, required_alarms, required_cooking_ft, cooking_deficit_ft, bath_deficit_ft