NTC Thermistor Resistance to Temperature (Beta Equation)

The temperature an NTC thermistor's measured resistance corresponds to.

Run the calculator

Example

You enter

You get

Details, formula, and sources

by the beta (B-parameter) equation 1/T = 1/T0 + (1/B) ln(R/R0) in kelvin. R0 is the nominal resistance at the reference temperature T0 (almost always 10 kohm at 25 C for the HVAC-standard sensor) and B (~3435-3950 K) is the material constant, both off the datasheet. Being NEGATIVE-coefficient, resistance FALLS as temperature RISES: a 10 kohm/3950 K sensor reads 25 C at 10 kohm, 41.5 C at 5 kohm, 10.2 C at 20 kohm. The beta form is a two-point fit good to about +/-0.2-1 C near T0; a wider or tighter job uses the 3-constant Steinhart-Hart. Distinct from a platinum RTD (positive-coefficient, Callendar-Van Dusen). The datasheet R-T curve, tolerance, and self-heating govern the field accuracy.

1/T = 1/T0 + (1/B) ln(R/R0), T and T0 in kelvin (T0 = ref_temp_c + 273.15); T = 1 / (1/T0 + (1/B) ln(R/R0)); output in C and F. R0 and B come from the sensor datasheet.

NTC thermistor beta (B-parameter) resistance-temperature equation, by name; the sensor datasheet R-T curve and tolerance govern. A wider span uses the 3-constant Steinhart-Hart equation.

The beta equation is public (a two-point Arrhenius fit); R0 (e.g. 10 kohm at 25 C) and B (e.g. 3950 K) are the two datasheet numbers for the specific thermistor, and R is the field reading.

Estimate. AHJ and licensed professional govern.

Field names used by the API: resistance_ohms, r0_ohms, beta_k, ref_temp_c, temperature_c, temperature_f