Window Solar Heat Gain and Conduction Cooling Load

The two ways a window adds to a cooling load.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The solar radiation through the glass (area x SHGC x peak solar factor) and the conduction driven by the indoor-outdoor difference (area x U x CLTD). On a west wall in summer the solar term dwarfs the conduction by an order of magnitude, which is why orientation and SHGC, not U-value, drive a glass cooling load - the number to diagnose a hot room or justify a shading or low-SHGC retrofit. The peak solar factor is read from the ASHRAE/ACCA table for the orientation and latitude. One Manual J component, not the stamped load sheet.

q_solar = area_ft2 x shgc x psf; q_cond = area_ft2 x u_factor x cltd_f; q_total = q_solar + q_cond.

ASHRAE / ACCA Manual J fenestration cooling load (Q_solar = A x SHGC x PSF, Q_cond = A x U x CLTD), by name; the relations are public.

The fenestration solar and conduction cooling-load relations are public ASHRAE / ACCA Manual J equations; the SHGC and U come from the NFRC label.

Estimate. AHJ and licensed professional govern.

Field names used by the API: area_ft2, shgc, psf, u_factor, cltd_f, q_solar, q_cond, q_total