Coil Bypass Factor and Apparatus Dew Point

How much air slips past a coil untouched, and how much actually contacts it.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Bypass factor BF = (t_lvg - t_adp)/(t_ent - t_adp), contact factor CF = 1 - BF, off the apparatus dew point (coil-surface temperature). 80 -> 55 F off a 50 F ADP -> BF 0.167, CF 0.833; a shallower coil bypasses more and dehumidifies worse. A design aid; the coil rating governs.

BF = (t_lvg - t_adp) / (t_ent - t_adp); CF = 1 - BF.

The coil bypass / contact factor and apparatus-dew-point definition from the ASHRAE Handbook - Fundamentals, by name.

The bypass-factor / apparatus-dew-point construction is a standard coil-performance result. The coil rating and ADP selection govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: t_ent_f, t_lvg_f, t_adp_f, bf, cf