Condensing Appliance Flue Condensate Rate

The condensate a high-efficiency condensing furnace, boiler, or water heater drains.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The number that sizes the drain, condensate pump, and neutralizer. Natural gas MAKES water (CH4 -> 2 H2O), ~9.4 lb per therm (100,000 BTU): a 100,000 BTU/hr appliance produces ~9.4 lb/hr of water vapor. A condensing appliance cools the flue below its dew point to recover latent heat, condensing a fraction (~0.8-0.9 at design return temps), so condensate = (input/100,000) x water-per-therm x condensing fraction / 8.34 lb/gal = ~0.96 gph per 100,000 BTU/hr, ~1.5 gph for a 150,000 BTU/hr boiler. The condensate is mildly acidic (pH ~3-5), so codes increasingly require a limestone/marble neutralizer before cast-iron/copper drains or septic, and the drain must be trapped, pitched, and freeze-protected. A sizing aid; the rated condensate output, the plumbing code (drain/trap/neutralizer), and the manufacturer govern.

therms_per_hr = input_btu_hr / 100000; water_produced_lb_hr = therms_per_hr x water_lb_per_therm; condensate_gph = water_produced_lb_hr x condensing_fraction / 8.34. Natural gas produces ~9.4 lb water per therm.

Condensing appliance flue condensate rate from the water of combustion (methane stoichiometry) and the condensing fraction, by name; the appliance's rated condensate output, the local plumbing code (drain, trap, neutralizer), and the manufacturer's instructions govern.

The water-of-combustion stoichiometry (CH4 + 2 O2 -> CO2 + 2 H2O) is public physics; the fuel input, the water per therm, and the condensing fraction are the appliance's operating values.

Estimate. AHJ and licensed professional govern.

Field names used by the API: input_btu_hr, water_lb_per_therm, condensing_fraction, water_produced_lb_hr, condensate_gph