Evaporator Defrost Heat and Cycle Time

How much heat a defrost takes and how long it runs, from the three terms that make it up.

Run the calculator

Example

You enter

You get

Details, formula, and sources

They are not the same size: melting the ice costs 144 BTU per pound against about 21 to warm that same ice from a freezer coil's temperature up to 32 F, so the latent term dominates -- but the coil warm-up term is the one that gets forgotten, and on a large coil with heavy fin stock it is real. Defrost efficiency captures everything that is NOT melting frost: heat going into the box instead of the coil, into the drain pan, and out through the insulation, and on electric defrost it is commonly only 60% to 80%. The last relation closes the loop, because frost accumulates at the coil's moisture removal rate, which is set by the box's latent load -- door openings, product respiration, infiltration. That determines how much frost is on the coil when defrost initiates, which determines how long defrost takes, so a box with heavy traffic needs more defrosts and each one is longer, and every minute of defrost is a minute of heat going into a freezer. A freezer coil at -10 F with 20 lb of frost, 60 lb of coil warmed 60 F, a 3 kW heater and 80% efficiency needs 4,575 BTU and runs 26.8 minutes, which lines up with the 20 to 30 minute terminations most controllers are set to. But halve the frost by fixing a door gasket and it falls to 14.7 minutes; double it and it climbs to 51.0. A fixed termination time is right for exactly one frost load, which is the argument for demand defrost. A sizing estimate; the manufacturer's defrost data and a measured coil temperature at termination govern.

sensible_btu = frost_lb x 0.5 x (32 - coil_temp_f); latent_btu = frost_lb x 144; coil_warmup_btu = coil_mass x specific_heat x rise; total_btu = (sensible + latent + coil warm-up) / defrost_efficiency; defrost_min = total_btu / heater_btuh x 60.

Defrost heat from the sensible, latent, and coil warm-up terms -- 144 BTU/lb to melt ice, about 0.5 BTU/lb-F to warm it to 32 F -- divided by the defrost efficiency, by name; public thermodynamics with the efficiency entered rather than bundled. The equipment manufacturer's defrost data and a measured coil temperature at termination govern.

The latent heat of fusion and the specific heat of ice are public physical constants; the frost load, coil mass, heater rating, and efficiency are the system's own values.

Estimate. AHJ and licensed professional govern.

Field names used by the API: frost_lb, coil_temp_f, coil_mass_lb, coil_specific_heat, coil_temp_rise_f, heater_btuh, defrost_efficiency, sensible_btu, latent_btu, coil_warmup_btu, total_btu, defrost_min