Walk-In Cooler Heat Load

Box load = transmission (U x area x deltaT) + infiltration + product + internal, times a safety factor. U 0.05, 800 ft^2, 60 F, +3000/5000/1500, 1.10 -> 2,400 transmission, 13,090 Btu/hr (1.09 tons); a 6 in panel (U 0.03) cuts it to 12,034. Size the evaporator for an ~18 hr run. The box-load method and equipment ratings govern.

Run the calculator

Formula and source

transmission = U x area x deltaT; total = (transmission + infiltration + product + internal) x safety; tons = total / 12000.

The walk-in cooler/freezer box heat-load method (transmission + infiltration + product + internal, with a safety factor), from ASHRAE Refrigeration, by name.

Audience

This tile is built for trades and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.