Walk-In Cooler Heat Load

Box load = transmission (U x area x deltaT) + infiltration + product + internal, times a safety factor.

Run the calculator

Example

You enter

You get

Details, formula, and sources

U 0.05, 800 ft^2, 60 F, +3000/5000/1500, 1.10 -> 2,400 transmission, 13,090 Btu/hr (1.09 tons); a 6 in panel (U 0.03) cuts it to 12,034. Size the evaporator for an ~18 hr run. The box-load method and equipment ratings govern.

transmission = U x area x deltaT; total = (transmission + infiltration + product + internal) x safety; tons = total / 12000.

The walk-in cooler/freezer box heat-load method (transmission + infiltration + product + internal, with a safety factor), from ASHRAE Refrigeration, by name.

The four-component box-load method is standard published refrigeration practice; the ASHRAE Handbook - Refrigeration covers it.

Estimate. AHJ and licensed professional govern.

Field names used by the API: u_factor, area_ft2, delta_t_f, infiltration_btuh, product_btuh, internal_btuh, safety, transmission_btuh, total_btuh