Evaporator Design TD and Humidity Band

The design split between box temperature and suction, and the humidity it holds in the box.

Run the calculator

Example

You enter

You get

Details, formula, and sources

DTD = box temp - saturated suction, which sets the box humidity: <=10 F ~90% RH (produce), 12-16 F ~75-80% (meat), >16 F <70% (frozen). A 35 F box on a 25 F SST -> 10 F TD, ~90% RH; a drying 17 F suction -> 18 F TD, <70% RH. A smaller TD needs more coil. The coil rating at the design TD governs.

DTD = box_temp - saturated_suction_temp; humidity band by DTD (<=10 F ~90% RH ... >16 F <70% RH).

The evaporator design temperature difference (DTD) and the resulting box-humidity bands, from refrigeration coil-selection practice, by name.

The DTD-to-humidity relationship is standard published refrigeration coil-selection guidance.

Estimate. AHJ and licensed professional govern.

Field names used by the API: box_temp_f, sst_f, dtd