Equipment Power Draw vs Circuit Capacity

Total continuous amperage from LGR dehumidifier / air-mover / HEPA-scrubber / heat-dryer counts (representative nameplate defaults), the NEC 210.20(A) 80%-continuous limit per breaker, and the number of 15 / 20 / 30 A circuits required, flagging any single unit too large for its own circuit. Per NEC 2023.

Run the calculator

Formula and source

Total continuous draw (A) = sum(quantity × nameplate amps) + other load. Continuous-load limit per circuit = 0.80 × breaker rating (NEC 210.20(A), continuous = 3 hr or more). Circuits required = ceil(total / (0.80 × breaker)). Total VA = total amps × circuit voltage.

NEC 2023 (NFPA 70) §210.20(A) (overcurrent protection for branch circuits) by section. Equipment nameplate amps are representative cut-sheet values (Phoenix / Dri-Eaz / B-Air class drying equipment).

Audience

This tile is built for restoration and the adjacent professions in the Water Damage and Mold Restoration group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.