Equipment Power Draw vs Circuit Capacity

Total amps drawn by drying equipment, and how many 15/20/30 A circuits it needs.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Total continuous amperage from LGR dehumidifier / air-mover / HEPA-scrubber / heat-dryer counts (representative nameplate defaults), the NEC 210.20(A) 80%-continuous limit per breaker, and the number of 15 / 20 / 30 A circuits required, flagging any single unit too large for its own circuit. Per NEC 2023.

Total continuous draw (A) = sum(quantity × nameplate amps) + other load. Continuous-load limit per circuit = 0.80 × breaker rating (NEC 210.20(A), continuous = 3 hr or more). Circuits required = ceil(total / (0.80 × breaker)). Total VA = total amps × circuit voltage.

NEC 2023 (NFPA 70) §210.20(A) (overcurrent protection for branch circuits) by section. Equipment nameplate amps are representative cut-sheet values (Phoenix / Dri-Eaz / B-Air class drying equipment).

NFPA 70 free read-only at nfpa.org/freeaccess; manufacturer cut sheets free at each vendor site.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: qty_air_mover, qty_lgr_dehu, breaker_A, voltage, total_amps, continuous_limit_A, circuits_required, total_va