Water Damage and Mold Restoration
51 calculators and reference tools for water damage and mold restoration. Every tool runs entirely in your browser. No account. No fee. No advertising. No tracking.
Tools in this group
- Psychrometric Calculator - Dew point, GPP, vapor pressure from temperature and RH.
- Drying Goal - Target indoor GPP based on outdoor conditions.
- Dehumidifier Sizing - Required pints per day by AHAM and field methods.
- Air Mover Placement - Number and CFM coverage by water class.
- Water Loss Class and Category - Plain-English categories 1, 2, 3 and classes 1 to 4.
- Material Drying Times - Typical drying times by material and contamination.
- Mold Growth Conditions - Risk by temperature, RH, and time.
- PPE Selection - Typical PPE by water category and contamination type.
- Mold Remediation Scope by Area - EPA / NYC DOHMH remediation level, containment, PPE tier, and clearance from affected square footage.
- IICRC S520 Condition Reference - The three S520 Conditions (normal ecology, settled spores, actual growth) in plain English.
- Antimicrobial Mix and Coverage - Concentrate and water split, per-tank dose, and tank fills from area, label coverage, and dilution (oz/gal or 1:N).
- Air Sample Run Time and Volume - Spore-trap run time, total sampled volume, and total pump time from calibrated flow and target volume.
- Dry Standard vs Affected Reading - Delta above the unaffected dry standard, a dry/wet verdict, and points still to remove from moisture-meter readings.
- Flood-Cut Demolition Take-Off - Drywall area removed, 4x8 sheet count, baseboard linear feet, and batt-insulation area from wall run and cut height.
- Standing Water Volume - Gallons, ft^3, and weight from affected area and depth.
- Negative Air Machine Sizing - Required CFM and unit count from room volume and target ACH.
- HEPA Scrubber Filter Life - Estimated filter days from CFM, runtime, and particulate category.
- Thermal Imager Delta-T Reference - Typical surface-temperature differentials for moisture, insulation, and electrical hotspots.
- Containment Air Balance - Required net negative CFM via Q = 2610 * A * sqrt(delta_P) and recommended NAM count.
- Drying Chamber Air Turnover - Actual ACH from air-mover and dehu CFM and gap to target ACH.
- Drying Log (IICRC S500 Boundary Test) - Multi-row drying log: ambient / chamber paired daily readings, per-day boundary-humidity pass (chamber GPP must trend below ambient GPP), chamber GPP trend slope (GPP/day), and dry-down completion estimate. Up to 14 readings. Per IICRC S500-2021.
- Equipment Power Draw vs Circuit Capacity - Total continuous amperage from LGR dehumidifier / air-mover / HEPA-scrubber / heat-dryer counts (representative nameplate defaults), the NEC 210.20(A) 80%-continuous limit per breaker, and the number of 15 / 20 / 30 A circuits required, flagging any single unit too large for its own circuit. Per NEC 2023.
- Drying-Chamber Fresh-Air / CO2 Buildup - Required fresh-air exchange (cfm) and air changes per hour to hold a target CO2, from a mass balance against the outdoor concentration. Per ASHRAE 62.1; complements chamber-turnover. IICRC S500 governs the drying plan.
- Moisture Removed by Grain Depression - Water-removal rate (lb/hr, pints/hr) and total water over the run from a dehumidifier's measured inlet/outlet grain depression and process airflow - an in-situ performance check.
- Evaporation Load / Dehu Demand - Estimated initial water load (gal and lb), first-24-hour removal target, and suggested AHAM dehumidifier pints from affected area, water class, and editable per-class load factors.
- Asbestos / Lead Abatement Containment Take-Off - Containment poly sheeting, the negative-air machine count for the required air changes, and the regulated-waste bag count from the room dimensions.
- Equilibrium Moisture Content of Wood - The moisture content wood drifts toward at a given air temperature and relative humidity, from the USDA Forest Products Lab (Hailwood-Horrobin) sorption equation - the reference a restoration drying setup moves a material toward. The exact value varies by species; the IICRC S500 dry standard and the dry, unaffected reference reading govern when a material is 'dry.'
- Wicking-Height Flood Cut and Demolition Takeoff - Turns a measured wall run and the flood-cut line into the demolition takeoff a tech writes on the wall before the saw comes out: linear feet of score cut, square feet of board removed, replacement 4x8 sheet count, cavity insulation area, and baseboard run. The moisture meter sets the cut line a few inches above the highest reading, per IICRC S500 practice (by name); these are the resulting quantities.
- Trapped Ceiling-Cavity Water Load and Collapse Screen - The distributed load (a foot of water is 62.4 psf), total weight, and volume of water trapped overhead in a sagging ceiling cavity, with a drain-before-entry screen. The threshold is an editable screen value, not a code capacity - the fastening, span, and a structural engineer govern; this decides whether to punch-drain from a safe distance before anyone works beneath the bulge.
- Field-Effective Dehumidifier Capacity at Chamber Grain Depression - Derates a nameplate AHAM pint rating to its field output as the chamber dries and the inlet grains fall, and turns the derate into the honest unit count - which goes UP, not down, as the chamber dries (the classic drying plateau). The operator reads the derate factor off the unit's own performance curve at the measured chamber GPP; the curve and psychrometric reality govern.
- S500 Class-of-Loss Screen by Wetted-Surface Fraction - Turns the wetted-surface field read (how much of the floor and wall is wet, how high it wicked, whether low-evaporation assemblies are wet) into a candidate IICRC S500 Class of water intrusion and the matching per-class evaporation factor that feeds the load tiles. A deterministic screen that proposes a Class and states the rationale; the inspector's classification and a moisture map govern.
- Desiccant Process-Airflow Sizing for Deep and Low-Temperature Drying - Sizes a desiccant dehumidifier by the process airflow needed to carry a target water-removal rate across the wheel at the deep grain depression it can hold - the deep / low-temperature and specialty Class 4 drying path the refrigerant sizing never covers, from the same psychrometric mass balance grains-removed uses in reverse. The manufacturer's performance map governs the achievable depression; reactivation air must be ducted outside.
- Drying-System Balance (Installed Dehu vs Evaporation Load) - Checks whether the installed dehumidification keeps up with the estimated evaporation load: the balance in pints/day, the capacity-to-load ratio against a target margin, and a balanced / no-margin / deficit verdict with the capacity to add. Closes the loop between evaporation-load and dehumidifier. Field capacity falls below the AHAM nameplate as the air dries; the restorer's daily monitoring and IICRC S500 govern.
- Bound Water in Wet Materials - Estimates the weight (lb) and volume (gal) of water held in affected materials that drying must evaporate, from the material volume, oven-dry density, and the moisture-content drop to the dry goal. Scopes equipment-days and validates the plan against the evaporation and dehumidifier sizing. Moisture content is dry-weight basis; meter readings and IICRC S500 govern.
- Disinfectant / Antimicrobial Contact (Dwell) Time Reference - Returns the label-typical wet contact (dwell) time for common EPA-registered antimicrobial classes (quat, accelerated hydrogen peroxide, bleach solution, phenolic, botanical/thymol) and the keep-wet and pre-clean rules that decide whether a disinfection claim is actually achieved. Antimicrobials are EPA-registered pesticides whose label is the legal authority (FIFRA); the ranges are guidance and S500/S520 govern.
- Carpet / Cushion Restore-vs-Replace Decision (IICRC S500) - Maps water category, the affected component (carpet vs cushion), and delamination to the IICRC S500 restore-vs-replace decision with its rationale. Delaminated carpet is replaced; saturated cushion in any category is typically removed; Category 3 porous flooring is generally removed and disposed. A professional determination case by case; the restorer's judgment, customer agreement, and S500 govern.
- Water Category Deterioration Over Time (IICRC S500) - Applies the S500 principle that water category is determined at the time of remediation, not by the source alone: origin category, elapsed wet time, a warm-environment flag, and contaminant contact return the likely current category. A clean loss left standing or warm reclassifies upward; contaminant contact escalates toward Category 3. When in doubt the higher category is assumed; the restorer and S500 govern.
- Hydroxyl Generator Sizing by Volume (IICRC S700) - Sizes occupied-space hydroxyl deodorization by structure volume against a per-unit coverage rating: the generator count and the continuous run-time expectation. The occupied-safe counterpart to ozone shock and thermal fogging - hydroxyl radicals oxidize odor at safe occupied levels but work more slowly. Coverage and run times are manufacturer-specific; remove the source and clean first; the manufacturer and IICRC S700 govern.
- Injection / Wall-Cavity Drying System Sizing - Sizes an injection / wall-cavity drying system: the stud-bay count from the wall length and stud spacing, the injection port count, and the number of air-delivery systems - the minimally invasive alternative to a flood cut for drying enclosed assemblies in place. Port count and ports per system are manufacturer-specific; respect cavity contamination and pressure direction; the restorer and IICRC S500 govern.
- Drying Completion Projection (Days to Goal) - Projects how many days a material needs to reach its dry goal from the moisture-content drop observed between readings: the remaining points to goal and a constant-rate days-to-goal estimate, or a not-progressing flag when the daily drop stalls. Turns the drying log into a schedule. Drying is non-linear and slows near the goal; the drying-log readings and IICRC S500 govern the real pull date.
- Drying-Equipment Sensible Heat Load and Ventilation - Turns the air movers, dehumidifiers, and scrubbers running in a drying chamber into the sensible heat they dump (3.412 BTU/hr per watt) and the ventilation needed to hold a target temperature rise (the 1.08 sensible relation): the heat load, the makeup cfm to cap the rise, and the rise an entered exhaust airflow actually delivers. An overheated chamber leaves the efficient-evaporation band. Envelope losses and the building HVAC govern; this is a screen. IICRC S500 names the band.
- Fire-Exposed Wood Char Depth and Residual Capacity - Screens whether a charred wood beam or post kept enough sound section to carry load after a fire: the AWC/NDS one-dimensional char depth (about 1.5 in/hr) plus the heat-degraded zero-strength layer, the residual cross-section, and the bending-capacity (section-modulus) fraction that drives the keep-or-replace call. Heavy timber survives fire because the residual section is large. Screens the bending section only; a structural engineer governs connections, splitting, and the load path.
- Dry-Sponge Soot Cleaning Takeoff and Seal Coat - Turns soot-affected wall and ceiling area into the chemical sponges, labor hours, and odor-seal primer the dry-smoke cleaning phase consumes: sponges from a per-sponge coverage, labor from a production rate, and primer gallons from a coverage rate. The residue type governs the method, so dry sponging is for dry smoke; protein, wet, and fuel-oil residues need wet cleaning. A quantity screen for a fire estimate, not a cleaning protocol. IICRC S700 governs.
- Ozone Deodorization Sizing, Time, and Lockout - Sizes an ozone shock-deodorization for smoke odor in an unoccupied structure by treatable volume against each unit's rated volume, with the safety lockout front and center: the generators needed, the shock duration, and the unoccupied-sealed-aerate sequence. Ozone is a strong oxidizer and respiratory toxin; the space must be sealed and aired below the 0.1 ppm OSHA limit before reentry, and a hydroxyl generator is the occupied-space alternative. Sizes equipment; not authority to run ozone occupied.
- Smoke Residue Type and Cleaning Method Screen - Maps an observed smoke residue (dry, wet, protein, fuel-oil/puffback, or synthetic) to its cleaning method, the decision every fire job turns on before a sponge or solvent is chosen: the residue source, appearance, recommended method, deodorization note, and the trap to avoid (protein looks invisible but must not be dry-sponged). A test-clean of an inconspicuous area governs the final method; this screen narrows it. IICRC S700 governs.
- Thermal/ULV Fog Deodorizer Dosage - Sizes the deodorant a thermal or ULV fogging pass consumes, dosed by structure volume against a label rate in ounces per 1,000 cubic feet across one or more passes: the ounces to mix and the gallons. Fogging penetrates the porous paths the smoke took, the counterpart to ozone shock. The label rate and dwell govern; a thermal fogger produces a hot fog from an open flame, so the space is unoccupied and a fire watch applies. Sizes quantity only. IICRC S700 governs.
- Contents Pack-Out Volume, Boxes, and Storage - Turns an affected room's contents into the boxes, climate storage, and truck loads a pack-out requires: the contents volume from a density per floor area, the box count, the storage volume with a warehouse stacking allowance, and the truck loads. Serious fire and water losses begin with a pack-out so the structure can be cleaned and dried. The actual inventory and box mix govern; the densities are starting rules of thumb. An estimating screen.
- Surface Condensation Risk and Dew-Point Margin - The failure mode a psychrometric read never screens: warm, humid drying air meeting a cold single-pane window, uninsulated wall, or slab edge and condensing there - secondary water in the worst place for mold. Computes the Magnus dew point from the chamber air temperature and RH, compares it to the coldest surface (IR-read), and flags whether the surface sits at or below the dew point and by what margin. Lower the humidity or warm the surface to clear the risk. A screen; the IR-read surface temperature governs (ANSI/IICRC S500).
- Indoor/Outdoor Spore Ratio Clearance Screen - The everyday mold clearance read: post-remediation indoor airborne spore concentration should sit at or below the outdoor control (ratio at or under 1), with no indoor-dominant water-damage marker genera (Stachybotrys, Chaetomium) elevated inside. Computes the indoor/outdoor ratio and screens the marker flag. A screen, not a clearance certificate; an independent environmental professional interprets the genera and the full criteria (ANSI/IICRC S520).
- Hardwood Floor Drying-Mat System Sizing - Sizes the Class 4 specialty mat system that saves a wet wood floor without tearing it out: panels laid on the floor and pulled by a suction unit that draws moisture up through the boards. Gives the mats needed from the floor area and per-mat coverage, and the suction units to drive them. The mat-system manufacturer's coverage and unit ratings govern; subfloor construction and finish affect feasibility (ANSI/IICRC S500 Class 4 specialty drying).
- Mold Surface Remediation Labor and HEPA Vacuuming - The labor cost driver between the scope tier and the chemistry: the hours to physically clean remediated surfaces. S520 source removal is a multi-pass operation (HEPA vacuum, damp wipe, HEPA vacuum again) at a production rate the substrate and access set. Gives the labor-hours from area, passes, and production rate, and the crew calendar time. The Condition, substrate, and access govern the rate; non-cleanable porous materials are removed, not cleaned (ANSI/IICRC S520).