Negative Air Machine Sizing
Required CFM and unit count from room volume and target ACH.
Formula and source
Required Negative Air Machine CFM = chamber_volume_ft³ × target_ACH / 60. 4-6 ACH for general containment; 12+ ACH for active mold remediation per IICRC S520-2024 §12.
IICRC S520-2024 §12 (Engineering Controls) by name; ASHRAE 170 (Ventilation of Health Care Facilities) by name for hospital-equivalent ACH.
Audience
This tile is built for restoration and the adjacent professions in the Water Damage and Mold Restoration group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.
Related tools
Posture
Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.