Moisture Removed by Grain Depression

Water a dehumidifier removes per hour and over the run, from its grain depression and airflow.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Water-removal rate (lb/hr, pints/hr) and total water over the run from a dehumidifier's measured inlet/outlet grain depression and process airflow - an in-situ performance check.

dG = inlet_GPP - outlet_GPP; mass-air = CFM*60/13.33 lb-dry-air/hr; water lb/hr = mass-air * dG / 7000 (7000 grains/lb); gal = lb/hr * hours / 8.345.

First-principles psychrometric mass balance (7000 grains/lb; ~13.33 ft3/lb dry air); IICRC S500 grain-depression field method, by name.

Public psychrometric constants; IICRC S500 governs the drying plan.

Estimate. AHJ and licensed professional govern.

Field names used by the API: cfm, inlet_gpp, outlet_gpp, hours, water_lb_hr, water_gal