Gas Appliance Connection Check (IFGC 408.4 / 409.5 / 411.1.3.1)

Three rules meet at the last three feet of gas piping, and one category cuts across all of them.

Run the calculator

Example

You enter

You get

Details, formula, and sources

409.5 puts the shutoff in the SAME ROOM, within 6 ft, and UPSTREAM of the union or connector -- a valve downstream cannot isolate the part most likely to fail. 408.4 wants a sediment trap downstream of that shutoff, unless the appliance has one built in or is on the exemption list. 411.1.3.1 caps a connector at 3 ft. The pattern worth seeing: ranges and clothes dryers are exempt from the trap, get 6 ft of connector instead of 3, AND are deemed accessible with the shutoff behind them. The code has a coherent idea of a MOVABLE appliance, and spotting it predicts all three answers instead of memorising three lists -- the same furnace that fails on a missing trap and a 4 ft connector passes as a dryer.

shutoff passes when it is in the same room, within 6 ft of the appliance, and upstream of the union or connector; a sediment trap is required unless the appliance type is excepted or a trap is incorporated in the appliance; connector length limit is 6 ft for ranges and domestic clothes dryers and 3 ft otherwise.

IFGC 409.5 (appliance shutoff valve location, and the allowance treating a shutoff behind a movable appliance as accessible), IFGC 408.4 (sediment trap, with its exception list), and IFGC 411.1.3.1 (maximum connector length).

All three are short prescriptive sentences reproduced in municipal adoptions and inspection checklists. No table is reproduced.

Estimate. AHJ and licensed professional govern.