Fuel-Gas Pipe Capacity (Spitzglass)

The most gas a bore carries within an allowable pressure drop.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Q = 3550 sqrt(dH D^5 / (SG L K')), K' = 1 + 3.6/D + 0.03 D. A 1 in bore (ID 1.049), 100 ft, 0.6 SG natural gas at a 0.5 in w.c. allowable drop carries 173 CFH at 480 fpm. A longhand alternative to the NFPA 54 / IFGC capacity tables; the actual bore, not nominal, and NFPA 54 governs. Flags a drop above the ~1.5 psi low-pressure range.

Spitzglass low-pressure solved for the flow: Q = 3550 * sqrt((dH * D^5) / (SG * L * K')), K' = 1 + 3.6/D + 0.03*D. dH (in w.c.), D (in actual bore), L (ft), SG. Velocity from Q and bore area.

Published Spitzglass low-pressure gas-flow equation (public engineering formula); the inverse of the gas-pipe pressure-drop tile and a longhand alternative to the NFPA 54 / IFGC capacity tables, by name.

NFPA 54 free read-only at nfpa.org/freeaccess and codes.iccsafe.org; NFPA 54 governs the installation.

Estimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

Field names used by the API: drop_inwc, id_in, length_ft, sg, flow_cfh, velocity_fpm