Jockey (Pressure-Maintenance) Pump Sizing (NFPA 20)

The jockey pump flow and the staggered pressure-switch settings for a fire-pump system, per NFPA 20 practice.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Jockey flow is small (about 1% of the fire pump's rated flow, at least 1 gpm) so it makes up leakage without the fire pump starting on every drop -- a 750 gpm fire pump takes about a 7.5 gpm jockey. The switches stagger so the jockey acts first: jockey stop = fire-pump churn (shutoff) pressure + minimum static supply (170 psi for a 120 psi churn and 50 psi static); jockey start = stop - 10 (160); fire-pump start = jockey start - 5 (155). A too-large jockey masks a real flow and fails to start the fire pump on a fire. A settings guide; NFPA 20, the pressure switches, and the AHJ / stamped fire-pump design govern.

jockey_gpm = max(0.01 x fire_pump_gpm, 1); jockey_stop_psi = churn_psi + min_static_psi; jockey_start_psi = jockey_stop_psi - 10; fire_pump_start_psi = jockey_start_psi - 5.

NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) pressure-maintenance (jockey) pump practice, by name; the pressure-switch settings and the AHJ govern.

The jockey-flow rule of thumb and the staggered pressure-switch offsets are public NFPA 20 practice; the fire-pump rating, churn pressure, and static supply come from the pump data and the water supply.

Estimate. AHJ and licensed professional govern.

Field names used by the API: fire_pump_gpm, churn_psi, min_static_psi, jockey_gpm, jockey_stop_psi, fire_pump_start_psi