Max Microinverters per AC Branch Circuit (NEC 705.60)

The most microinverters or AC modules on one AC branch circuit.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Their combined continuous output, as a continuous load, cannot exceed 80% of the branch overcurrent device (NEC 705.60 / 690.8(B) / 240.4), so N = floor(OCPD x 0.80 / unit max current). A 20 A branch with an Enphase IQ7+ at 1.21 A allows 13 microinverters; a 1.0 A unit allows 16, a higher-output unit fewer. Use the unit's MAXIMUM continuous AC output current from its datasheet, not the panel wattage over voltage, and size the branch conductors and the point-of-connection to the same 125% continuous rule. The microinverter datasheet, the AHJ, and the adopted NEC edition govern.

continuous_limit_a = branch_ocpd_a x 0.80; max_microinverters = floor(continuous_limit_a / unit_max_current_a); branch_load_a = max_microinverters x unit_max_current_a.

NEC 705.60 (interconnected sources), 690.8(B) (continuous current), and 240.4 (conductor / OCPD protection), by name; the microinverter datasheet and the adopted NEC edition govern.

The 80% continuous limit is public NEC (many jurisdictions post the adopted NEC); the unit's maximum continuous AC output current comes from its datasheet.

Estimate. AHJ and licensed professional govern.

Field names used by the API: branch_ocpd_a, unit_max_current_a, max_microinverters, continuous_limit_a