Feeder Sizing for Multiple Motors

Feeder conductor (NEC 430.24) and feeder overcurrent device (NEC 430.62) for several motors on one feeder.

Run the calculator

Example

You enter

You get

Details, formula, and sources

With the largest-motor term shown.

Feeder conductor (NEC 430.24) >= 1.25 * FLC_largest + sum(FLC_other) + non-motor load. Feeder OCPD (NEC 430.62) <= largest_branch_device + sum(FLC_other), not rounded up (next standard size down where the sum is not a standard rating).

Feeder conductor and feeder overcurrent sizing for several motors on one feeder per NEC 430.24 and 430.62, by name; table FLC (not nameplate FLA) per 430.6(A). The AHJ-adopted NEC edition governs.

NEC is free to read at nfpa.org/freeaccess. Table FLC and branch-device ratings are user-supplied.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: motors, conductor_min_A, feeder_ocpd_max_A