Motor Starting Voltage Dip

Voltage dip during motor start from locked-rotor current and conductor length.

Run the calculator

Example

You enter

You get

Details, formula, and sources

With terminal voltage and a pass/fail against the dip limit (contactor dropout risk).

V_drop = (2 for 1-phase, sqrt(3) for 3-phase) x K x LRC x L / cmils; V_terminal = V_source - V_drop; %dip = V_drop / V_source x 100. K is the conductor constant (Cu ~12.9, Al ~21.2 ohm-cmil/ft) and LRC the motor locked-rotor current.

Ohm's-law voltage-drop method (first principles); motor locked-rotor current per NEC Article 430 code-letter tables; contactor pickup/dropout ~85% nominal per NEMA ICS 2, by name.

NFPA 70 free read-only at nfpa.org/freeaccess; LRC user-supplied from the nameplate code letter or estimated as 6x FLA.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: source_voltage_V, length_ft, cmils, lrc_A, phase, k_const, dip_limit_pct, v_drop_V, dip_pct, v_terminal_V

Related tools