Steam Main Capacity from Size and Velocity

How much steam an existing Sch 40 main carries within an allowable velocity.

Run the calculator

Example

You enter

You get

Details, formula, and sources

The inverse of the steam-main sizer: how much steam an existing Sch 40 main carries within an allowable velocity - capacity = velocity x 60 x internal area / specific volume, the area from the Sch 40 ID. A 2 in main (ID 2.067) at a 6,000 ft/min ceiling and 13.7 ft3/lb carries 612 lb/hr; a 4 in at the same velocity carries 2,323, so a load the sizer put in 4 in fits with margin. The velocity band (supply mains ~6,000-12,000 ft/min) is a recommendation, not a code limit; the engineer of record governs.

area_ft2 = (pi/4)(ID_in/12)^2 from the Sch 40 ID; capacity_lbhr = vel_ceiling_fpm x 60 x area_ft2 / spec_vol_ft3lb.

First-principles continuity, the inverse of the steam-main sizer; the recommended velocity band (supply mains ~6,000 to 12,000 ft/min) and the saturated-steam specific volumes are from ASHRAE Fundamentals / Systems, by name. Sch 40 IDs are ASME B36.10M nominal mill dimensions.

Continuity (volumetric flow / specific volume = mass flow) is public; the steam specific volume comes from the published saturated-steam table at the line pressure.

Estimate. AHJ and licensed professional govern.

Field names used by the API: nps, spec_vol_ft3lb, vel_ceiling_fpm, capacity_lbhr, area_in2