Voltage Drop With Reactance

Single- or three-phase voltage drop using NEC Chapter 9 Table 9 R and X per 1000 ft and the load power factor.

Run the calculator

Example

You enter

You get

Details, formula, and sources

With the 3% / 5% advisory band.

Vd = k * I * (R*cos(theta) + X*sin(theta)) * L / 1000, with k = 2 single-phase or sqrt(3) three-phase and theta = arccos(PF). R and X per 1000 ft are selected by conductor size and conduit material.

NEC 2023 (NFPA 70). Chapter 9 Table 9 (R and X per 1000 ft); 210.19(A) Note 4 (3% branch) and 215.2(A)(1) Note 2 (5% total) advisory bands.

Free read-only access at nfpa.org/freeaccess.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: system_voltage_v, current_a, length_ft, r_ohm_per_kft, x_ohm_per_kft, power_factor, phase, drop_v, drop_percent, voltage_at_load_v