Voltage Drop With Reactance

Single- or three-phase voltage drop using NEC Chapter 9 Table 9 R and X per 1000 ft and the load power factor, with the 3% / 5% advisory band.

Run the calculator

Formula and source

Vd = k * I * (R*cos(theta) + X*sin(theta)) * L / 1000, with k = 2 single-phase or sqrt(3) three-phase and theta = arccos(PF). R and X per 1000 ft are selected by conductor size and conduit material.

NEC 2023 (NFPA 70). Chapter 9 Table 9 (R and X per 1000 ft); 210.19(A) Note 4 (3% branch) and 215.2(A)(1) Note 2 (5% total) advisory bands.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.