Duct Heat Gain/Loss Through Unconditioned Space

Duct heat gain or loss through unconditioned space, and the supply-air temperature change.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Conductive duct heat gain/loss Q = U A dT (U = 1/R) and the resulting supply-air temperature change dT_air = Q/(1.08 CFM). 1,000 CFM of 55 F air in R-4 duct, 100 ft^2, a 120 F attic warms 1.5 F; R-8 halves it. Steady-state conduction, no leakage. A design aid.

U = 1/R_duct; Q = U A dT (Btu/h); dT_air = Q / (1.08 x CFM).

The conductive duct heat-gain/loss relation from the ASHRAE Handbook - Fundamentals duct-design method, by name.

The Q = U A dT conduction relation and the 1.08 sensible-air constant are standard ASHRAE / duct-design values. The ductwork design and ambient conditions govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: R_duct, A_ft2, dT_F, cfm, Q_btuh, dT_air