Grille/Register Face Velocity and Free-Area Sizing

Face velocity V = CFM/(gross area x free-area ratio), or the required gross size from a target velocity. 400 CFM to a 500 fpm supply -> 154 in^2 (a 12x14); returns run slower so they size larger. The manufacturer free-area and throw data govern.

Run the calculator

Formula and source

A_free = A_gross x ratio; V_face = CFM / A_free; A_gross_req = CFM / (V_target x ratio).

The grille/register free-area face-velocity relation from ASHRAE / SMACNA air-distribution practice, by name.

Audience

This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.