Grille/Register Face Velocity and Free-Area Sizing

Face velocity V = CFM/(gross area x free-area ratio), or the required gross size from a target velocity.

Run the calculator

Example

You enter

You get

Details, formula, and sources

400 CFM to a 500 fpm supply -> 154 in^2 (a 12x14); returns run slower so they size larger. The manufacturer free-area and throw data govern.

A_free = A_gross x ratio; V_face = CFM / A_free; A_gross_req = CFM / (V_target x ratio).

The grille/register free-area face-velocity relation from ASHRAE / SMACNA air-distribution practice, by name.

Face velocity = airflow / free area is a standard air-distribution relation; the free-area ratio and throw/NC data come from the manufacturer's published grille catalog. The manufacturer's selection data govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: mode, cfm, ratio, V_target, A_gross_req_ft2, A_gross_req_in2