Motor Running Overload Protection (NEC 430.32)

The second of the two motor protection devices - the one motor-branch-protection defers: the running overload, sized on the NAMEPLATE FLA (not the table FLC the branch device uses). NEC 430.32(A)(1) gives 125% of FLA for a continuous-duty motor over 1 hp with a marked service factor of 1.15+ or a marked rise of 40 C or less, 115% otherwise, and 430.32(C) permits raising to 140%/130% only if the motor will not start at the base setting. A 26 A SF-1.15 motor sets at 32.5 A with a 36.4 A ceiling - the number dialed into the overload relay or the heater table. A design aid; the AHJ governs.

Run the calculator

Formula and source

hi_class = (sf >= 1.15) or (marked rise <= 40 degC); mult = hi_class ? 1.25 : 1.15; mult_max = hi_class ? 1.40 : 1.30; ol_A = fla_A x mult; ol_max_A = fla_A x mult_max.

Motor running-overload sizing on the nameplate full-load current under NEC 2023 430.32(A)(1) (125% for a marked service factor of 1.15 or more or a marked temperature rise of 40 degC or less, 115% otherwise) with the 430.32(C) will-not-start ceiling (140%/130%), by name. A computational aid; the AHJ-adopted NEC edition governs.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.