Required Fire Flow
ISO method from square footage and exposure.
Example
You enter
- Structure area (ft²) 5000
- Construction class ordinary
- Occupancy factor 1
- Exposure factor 1
- Communication factor 1
You get
- Needed fire flow (ISO) 1250 gpm
- Base C 1273 gpm
- Construction factor 1
Details, formula, and sources
ISO Needed Fire Flow NFF = (C × O × X × P) where C = 18 × F × sqrt(A), F is construction-class factor, O is occupancy hazard, X is exposure factor, P is communication factor.
ISO Public Protection Classification (PPC) Schedule by name.
ISO PPC documents licensed; the per-class 0.6 / 0.8 / 1.0 / 1.2 / 1.5 F-factor multipliers are reproducible from ISO outreach materials.
Estimate. AHJ and licensed fire protection engineer govern.
Field names used by the API: structure_area_ft2, construction_class, occupancy_factor, exposure_factor, communication_factor, needed_fire_flow_gpm, base_C_gpm, construction_factor
- F / O / X / P tables data/fire/fire-flow-formulas.jsonISO PPC Schedule